The table lists minimum recommended cable specifications for indoor installations. Part numbers are examples only; equivalent cables meeting the stated requirements are acceptable.
| USAGE | CABLE TYPE | PART # |
| RS-485 (includes BACnet MS/TP & Modbus RTU) | 22 AWG, STRANDED, 2 COND, TWISTED PAIR, SHIELDED | 221-PRSP-BAC |
| 3-WIRE SENSOR CABLE | 22 AWG, STRANDED, 3 COND, SHIELDED | CL3P22/3-7S |
| INDUSTRIAL RS-485 | 22 AWG, STRANDED, 2 COND, TWISTED PAIR, SHLD, TINNED COPPER BRAID OVERALL | 3105A |
| 24 VAC POWER | 18 AWG, STRANDED, 2 COND, TWISTED, UNSHIELDED | 002321 |
| 2-WIRE AO / THERMISTOR INPUTS | 18 AWG, STRANDED, 2 COND, SHIELDED, STRANDED BARE OR TINNED COPPER | 002320 |
| 2-WIRE ANALOG/RELAY OUTPUTS | 18 AWG, STRANDED, 2 COND, SHIELDED, STRANDED BARE OR TINNED COPPER | 002320 |
| 3-WIRE ANALOG INPUTS | 18 AWG, STRANDED, 3 COND, SHIELDED, STRANDED BARE OR TINNED COPPER | 002330 |
| 3-WIRE ANALOG OUTPUTS | 18 AWG, STRANDED, 3 COND, SHIELDED, STRANDED BARE OR TINNED COPPER | 002330 |
| 4-WIRE ACTUATOR CABLE | 18 AWG, STRANDED, 4 COND, SHIELDED, STRANDED BARE OR TINNED COPPER | 002340 |
RS-485 Wiring Requirements
Trunk configuration and length
- Wire RS-485 communications in a point-to-point daisy-chain topology. T-taps, stubs, spurs, and star configurations are not permitted.
- Keep total trunk length to 200 feet or less.
- Keep the maximum distance between any two adjacent devices on a trunk to 50 feet or less.
- Connect no more than 32 devices to a single RS-485 trunk.
- Repeaters are not permitted.
Termination resistors
- Install a 120-ohm termination resistor at each end of the RS-485 trunk, connected across the positive (+) and negative (-) receiver terminals.
- Do not connect termination resistors to the third (ground/common) conductor or to the cable shield/drain wire.
- Note: ClimaVision devices are equipped with onboard end-of-line (EOL) resistor jumpers or dip switches. An external termination resistor is not required when ClimaVision devices are installed at both trunk ends. Ensure EOL jumper/dip switches are in the proper position.
Polarity
- RS-485 is polarity sensitive. Terminate positive (+) and negative (-) conductors to their correct respective terminals at all devices.
Shield and Drain Wire Termination
- Ground the cable shield/drain wire at one end of the trunk only, at the controller end. Leave the drain wire ungrounded at all other locations.
- At each intermediate device location, butt-splice the shield/drain wire and continue through to maintain shield continuity.
- At the ungrounded end of the trunk, wrap the drain wire a minimum of four (4) rotations around the outer cable jacket and secure with a minimum of two (2) wraps of electrical tape. Do not cut the drain wire short inside the cable jacket.
Common/Ground Conductor
- At each intermediate device location where a common terminal is not available, butt-splice and tape the common reference/ground conductor to maintain continuity.
- At the terminal end of a trunk, wrap and tape unused common reference conductors in the same manner specified for ungrounded drain wires. Do not cut short inside the cable jacket.
Cable Separation and Routing
- Do not run RS-485 communication cables in a conduit or cable bundle with conductors carrying 120 v or greater.
- Do not run RS-485 communication cables in a conduit or cable bundle with power-carrying conductors of any voltage.
- Do not share or connect the RS-485 common/ground conductor with ground conductors from power-carrying cables.
Control Wiring Guidelines
Cable Routing and Continuity
- Use a dedicated cable for each input or output. Do not share cables for multiple sensors or output signals.
- Run all cabling as home runs directly from the controller to the field device. Splices are not permitted.
- Install cable clear of all sharp objects and free of sagging.
- Install tie wraps in a manner that prevents pinching or deformation of the cable jacket.
- Label each cable clearly within 1/4 inch of the wire termination at both ends, using the tag name designated in the project documentation.
Conductor Color Code - Control Wiring
Color | Assignment |
| RED | POWER (24 VAC / 24 VDC) |
| WHITE | (+) VDC CONTROL SIGNAL |
| BLACK | (-) OR COM |
| GREEN | (+) ACTUATOR FEEDBACK |
Conductor Color Code - Thermostat Wiring 8-Conductor
Color | Assignment |
| RED | POWER |
| BLACK | COM |
| YELLOW | Y1 / COOLING STAGE 1 |
| BLUE | Y2 / COOLING STAGE 2 |
| GREEN | G1 / FAN ENABLE |
| WHITE | W1 / HEATING STAGE 1 |
| BROWN | W2 / HEATING STAGE 2 |
| ORANGE | O/B/G2 / FAN STAGE 2 OR REVERSING VALVE |
General requirements applicable to all cable:
- Use stranded bare copper or stranded tinned copper conductors only. Copper-clad aluminum (CCA) conductors are not permitted.
- All shielded cables must include a drain wire. Terminate the drain wire per section 3.4.
- Cable ratings must comply with applicable nec articles for the installation environment. Use plenum-rated (CMP) cable where required by code.
- These specifications apply to indoor installations only. Outdoor or direct-burial applications require cables rated for the applicable environmental conditions.
Comments
0 comments
Please sign in to leave a comment.