The table lists minimum recommended cable specifications for indoor installations. Part numbers are examples only; equivalent cables meeting the stated requirements are acceptable.
 

USAGECABLE TYPEPART #
RS-485 (includes BACnet MS/TP & Modbus RTU)22 AWG, STRANDED, 2 COND, TWISTED PAIR, SHIELDED221-PRSP-BAC
3-WIRE SENSOR CABLE22 AWG, STRANDED, 3 COND, SHIELDEDCL3P22/3-7S
INDUSTRIAL RS-48522 AWG, STRANDED, 2 COND, TWISTED PAIR, SHLD, TINNED COPPER BRAID OVERALL3105A
24 VAC POWER18 AWG, STRANDED, 2 COND, TWISTED, UNSHIELDED002321
2-WIRE AO / THERMISTOR INPUTS18 AWG, STRANDED, 2 COND, SHIELDED, STRANDED BARE OR TINNED COPPER002320
2-WIRE ANALOG/RELAY OUTPUTS18 AWG, STRANDED, 2 COND, SHIELDED, STRANDED BARE OR TINNED COPPER002320
3-WIRE ANALOG INPUTS18 AWG, STRANDED, 3 COND, SHIELDED, STRANDED BARE OR TINNED COPPER002330
3-WIRE ANALOG OUTPUTS18 AWG, STRANDED, 3 COND, SHIELDED, STRANDED BARE OR TINNED COPPER002330
4-WIRE ACTUATOR CABLE18 AWG, STRANDED, 4 COND, SHIELDED, STRANDED BARE OR TINNED COPPER002340

 

RS-485 Wiring Requirements

Trunk configuration and length

  • Wire RS-485 communications in a point-to-point daisy-chain topology. T-taps, stubs, spurs, and star configurations are not permitted.
  • Keep total trunk length to 200 feet or less.
  • Keep the maximum distance between any two adjacent devices on a trunk to 50 feet or less.
  • Connect no more than 32 devices to a single RS-485 trunk.
  • Repeaters are not permitted.

Termination resistors

  • Install a 120-ohm termination resistor at each end of the RS-485 trunk, connected across the positive (+) and negative (-) receiver terminals.
  • Do not connect termination resistors to the third (ground/common) conductor or to the cable shield/drain wire.
  • Note: ClimaVision devices are equipped with onboard end-of-line (EOL) resistor jumpers or dip switches. An external termination resistor is not required when ClimaVision devices are installed at both trunk ends. Ensure EOL jumper/dip switches are in the proper position.

Polarity

  • RS-485 is polarity sensitive. Terminate positive (+) and negative (-) conductors to their correct respective terminals at all devices.

Shield and Drain Wire Termination

  • Ground the cable shield/drain wire at one end of the trunk only, at the controller end. Leave the drain wire ungrounded at all other locations.
  • At each intermediate device location, butt-splice the shield/drain wire and continue through to maintain shield continuity.
  • At the ungrounded end of the trunk, wrap the drain wire a minimum of four (4) rotations around the outer cable jacket and secure with a minimum of two (2) wraps of electrical tape. Do not cut the drain wire short inside the cable jacket.

Common/Ground Conductor

  • At each intermediate device location where a common terminal is not available, butt-splice and tape the common reference/ground conductor to maintain continuity.
  • At the terminal end of a trunk, wrap and tape unused common reference conductors in the same manner specified for ungrounded drain wires. Do not cut short inside the cable jacket.

Cable Separation and Routing

  • Do not run RS-485 communication cables in a conduit or cable bundle with conductors carrying 120 v or greater.
  • Do not run RS-485 communication cables in a conduit or cable bundle with power-carrying conductors of any voltage.
  • Do not share or connect the RS-485 common/ground conductor with ground conductors from power-carrying cables.

Control Wiring Guidelines

Cable Routing and Continuity

  • Use a dedicated cable for each input or output. Do not share cables for multiple sensors or output signals.
  • Run all cabling as home runs directly from the controller to the field device. Splices are not permitted.
  • Install cable clear of all sharp objects and free of sagging.
  • Install tie wraps in a manner that prevents pinching or deformation of the cable jacket.
  • Label each cable clearly within 1/4 inch of the wire termination at both ends, using the tag name designated in the project documentation.

Conductor Color Code - Control Wiring

Color

Assignment

REDPOWER (24 VAC / 24 VDC)
WHITE(+) VDC CONTROL SIGNAL
BLACK(-) OR COM
GREEN(+) ACTUATOR FEEDBACK

Conductor Color Code - Thermostat Wiring 8-Conductor

Color

Assignment

REDPOWER
BLACKCOM
YELLOWY1 / COOLING STAGE 1
BLUEY2 / COOLING STAGE 2
GREENG1 / FAN ENABLE
WHITEW1 / HEATING STAGE 1
BROWNW2 / HEATING STAGE 2
ORANGEO/B/G2 / FAN STAGE 2 OR REVERSING VALVE

 

General requirements applicable to all cable:

  • Use stranded bare copper or stranded tinned copper conductors only. Copper-clad aluminum (CCA) conductors are not permitted.
  • All shielded cables must include a drain wire. Terminate the drain wire per section 3.4.
  • Cable ratings must comply with applicable nec articles for the installation environment. Use plenum-rated (CMP) cable where required by code.
  • These specifications apply to indoor installations only. Outdoor or direct-burial applications require cables rated for the applicable environmental conditions.

 

Previous
Next

Comments

0 comments

Please sign in to leave a comment.

Was this article helpful?

0 out of 0 found this helpful
Powered by Zendesk