Overview
The CCU XR supports integration with RS485-based protocols such as Modbus RTU and BACnet MS/TP through its USB-A port. To enable this functionality, a USB-to-RS485 converter is required.
ClimaVision offers a supported adapter (7C-ND-C1W-X), to simplify deployment and ensure compatibility for customers integrating third-party RS485 devices.
Use Cases
This adapter enables the CCU XR to communicate with external RS485 devices, including:
- Modbus RTU devices (e.g., energy meters, power monitors)
- BACnet MS/TP devices (e.g., third-party controllers, RTUs)
System Architecture
- The converter plugs into the USB-A port on the CCU XR
- RS485 wiring connects from the adapter to the field bus
- Communication is configured within the CCU XR for the selected protocol
Multi-Protocol Support
The CCU XR can support multiple RS485 networks simultaneously with the use of USB hubs.
Key Capabilities
- Supports up to two USB hubs
- Supports multiple USB-to-RS485 adapters
- Allows communication with multiple protocols at the same time
- Example:
- Modbus RTU on one RS485 network
- BACnet MS/TP on another RS485 network
- Example:
Device Limitations
Total Device Count
- Recommended maximum: ≤ 40 total devices per CCU XR
Important:
The total device count includes all connected devices, not just third-party devices:
- ClimaVision devices
- Modbus devices
- BACnet MS/TP devices
Formula:
Total Devices =
ClimaVision Devices + Modbus Devices + BACnet Devices ≤ 40 (recommended)
Summary
The USB-to-RS485 adapter enables flexible integration of RS485-based devices with the CCU XR. By supporting multiple adapters via USB hubs, the CCU XR can communicate with both Modbus RTU and BACnet MS/TP devices simultaneously.
However, system design must account for total device limits and network performance to ensure reliable operation.
Comments