When using Non-Carrier manufactured sensors on ClimaVision products, the following are the minimum specifications in order to remain compliant with Carrier standards. 

If installed components do not meet/exceed these specifications, Carrier does not guarantee performance and may void warranty.

 

Actuators

Damper Type Electrical
Nominal Voltage AC/DC 24V
Nominal Frequency 50/60 Hz
Nominal Voltage Range AC: 19.2 - 28.8VDC: 21.6 - 28.8V
Power Consumption in Operation NTE 1.5W
Power Consumption in Rest Position NTE 0.4W
Transformer Sizing 3 VA
Overload Protection Electronic throughout 0-95° rotation
Torque Motor 45 in-lb (5 Nm)
Operating Range 0.5-10VDC
Input Impedance 100 kOhms
Position Feedback 0.5v-1.0v
Direction of Motion Motor Selectable with switch 0/1
Manual Override External Push Button
Angle of Rotation Max 95° w/ mechanical stop
Running Time (Motor) 90s @ 90°
Noise Level, Motor 35 dB(A)
Position Indication Mechanical
Power Source UL Class 2 Supply
Degree of Protection IEC/EN IP54
Degree of Protection NEMA/UL NEMA 2
Enclosure UL Enclosure Type 2
Agency Listing cULus acc. To UL60730-1A/-2-14, CAN/CSA E60730-1:02CE acc. To 2014/30/EU and 2014/35/EU
Quality Standard ISO 9001
UL 2043 Compliant Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient Humidity Max. 85% RH, non-condensing
Ambient Temperature -22 - 122°F
Storage Temperature -40-176°F
Servicing Maintenance Free
Weight 0.91 lb
Housing Material UL94-5VA
Rated Impulse Voltage 800V, Type Action 1, Control Pollution Degree 3

 

 

Proportional control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to a shaft from 1/4” to 5/8”. Actuators must provide control in response to a control input from an electronic controller or positioner. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be cULus listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo.

 

CTs

Sensor Range 0-10a, 0-20a, 0-50a, 0-100a, or 0-150a @ 0-10vdc
Operating Temperature -30 to 140°F
Sensor Type Internal w/ 0-10vdc Output
Accuracy +/- 2% FS (5% - 100% Span)
Max Sense Voltage 600 Vac
Frequency 10-400 Hz
Approvals UL Listed, UL916, CE, RoHS

 

Differential Pressure Sensors

Supply Voltage 15-36 VDC into > 5k Ohm Load/24VAC (+/- 10%), 50/60 Hz
Supply Current 6 mA maximum (0.18 VA)
Output Signals 0-10VDC: 3-wire, VAC or VDC Powered
Response Time (0-100% FSO) 4 Seconds
Accuracy +/- 0.25% FSO / °F
Thermal Effects +/- 0.067% FST / °F
Operating Temperature Range -4 to 185°F
Compensated Temperature Range 32 to 185°F
Operating Humidity 10 to 95% RH
Pressure Fitting Material Nickel Plated Brass
NIST Certification 3 Point NIST Test Points: 10%, 50%, 90% FSO5 Point NIST Test Points: 10%, 30%, 50%, 70%, 90% FSO
Approvals CE, RoHS2, WEEE, Reach

 

Temperature Sensors

Sensor Type Thermistor
Sensor Curve Non-Linear NTC
Number Wires Two (Non-Polarity Sensitive
Sensor Output @ 77°F 10KW Type II nominal
Sensor Accuracy @ 32-158°F +/- 0.36°F
Power Dissipation Constant 3 mW/°C
Response Time (63% Step Change) 10 Seconds nominal
Operating Temperature Range -40 to 185°F
Operating Humidity Range 10 to 95% RH, non-condensing
Storage Temperature Range -40 to 185°F
Probe Material 304 Stainless Steel
Agency Approvals CE, RoHS2, WEEE

 

CO2 Sensors

Supply Voltage 24 VAC/VDC ±20%; 50/60Hz (Half-wave rectified)
Power Consumption <1W
Electrical Connections 0.00232 in2 (1.5 mm2) screw terminals
Operating Temperature 32oF to 122oF (0oC to 50oC)
Operating RH 0 – 95% RH Non-condensing
Warm-Up Time 1 minutes (@ full specs 15 minutes)
Accuracy1 ±30 ppm and ±3% of reading
Repeatability ±20 ppm ±1% of measured value
Annual Zero Drift ± 0.3% of measurement range
Operating Pressure +1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa))
Sensing Method Single beam Non-dispersive Infrared (NDIR)
Sensor Life2 >15 years
Response Time <10 seconds @ 30 cc/min flow rate, < 3 minutes diffusion time
Operating Environment Residential, Commercial and Industrial spaces
Sensing Range 0 to 2000 ppm
Extended CO2 Ranges Up to 10,000 ppm (factory set or SADK Kit required)
Extended Range Accuracy >2,000 PPM +/- 30 ppm and +/- 5% of reading
Display (Optional) 4 digits, 7 segments LCD with ppm indicator
Calibration3 Senseair ABC algorithm (Automatic Baseline Correction)
Output Standard: Out 1: 0-10V for 0-2000 ppm
Storage -40 to 158oF (-40 to 70oC) Non-display, -4 to 122oF (-20 to 50oC) Display
Enclosure Duct Box: IP65 rated, PC & ABS blend, Flammability Rating UL94V-0 Cover: Makrolon® 6555 plastic, Flammability Rating UL94V-0 Pipe: PC & ABS blend, Flammability Rating UL94V-0
Room Dimensions (H) 5.95” (151.8 mm) x (W) 3.33” (84.6 mm) x (D) 1.85” (47 mm)
Product Weight 0.80 lbs (0.36 kg)
Agency Approvals EMC Directive 2014/30/EC

 

Pipe Temperature Sensors - Strap
Sensor Type Thermistor
Sensor Curve Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points One
Number Wires Two (Non-Polarity Sensitive)
Sensor Series Output @ 25oC (77oF) (Type II): 10KΩ nominal
Accuracy 0-70oC (32-158oF) +/-0.2oC (+/-0.36oF) except A/10K-E1 Series: +/-0.3oC (+/-0.54oF); A/1.8K Series: +/- 0.5oC @ 25oC (77oF) and (+/-1.0oC) (+/-1.8oF) Sensor Dependent; Contact ACI for more information on specific sensor
Stability 30 Seconds nominal
Power Dissipation Constant 3 mW/oC except A/1.8K Series: 1 mW/oC
Enclosure Specifications, Operating Temperature Range, Ratings Galvanized Steel, -40 to 93oC (-40 to 200oF), NEMA 1 (IP 10)
Storage Temperature Range -40 to 80oC (-40 to 176oF)
Operating Humidity Range 10 to 95% RH, non-condensing
Pipe Mount Sensor Enclosure Material 14” (35.6cm)
Foam Material Flammability Rating
Lead Length Conductor Size
Lead Wire Insulation Wire Rating
Conductor Material Silver Plated Copper
Product Weight 0.80 lbs. (0.37kg)
Agency Approvals CE, RoHS2, WEEE

 

Immersion Temp Sensor
Sensor Type Thermistor
Sensor Curve Non-Linear, NTC (Negative Temperature Coefficient)
Number Wires Two (Non-Polarity Sensitive)
Sensor Output @ 25°C (77°F) A/CP (Type II): 10KΩ nominal
Accuracy 0-70°C (32-158°F) +/-0.2oC (+/-0.36oF) except A/10K-E1 Series: +/- 0.3oC (+/-0.54oF) A/1.8K Series: +/-0.5oC @ 25oC (77oF) and (+/-1.0oC) (+/-1.8oF)
Response Time (63% Step Change) 10 Seconds nominal
Power Dissipation Constant 1 mW/oC
Sensor Operating Temperature Range -40 to 302oF
Operating Humidity Range 10 to 95% RH, non-condensing
Conductor Material Silver Plated Copper
Agency Approvals CE, RoHS2, WEEE

 

Outside Air Temperature Sensor
Sensor Type Thermistor
Sensor Curve Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points One
Number Wires Two (Non-Polarity Sensitive)
Sensor Series Output @ 25oC (77oF) (Type II): 10KΩ nominal
Accuracy 0-70oC (32-158oF) +/-0.2oC (+/-0.36oF)
Stability 30 Seconds nominal
Power Dissipation Constant 1 mW/oC
Enclosure Specifications, Operating A/XX-S-GD: Galvanized Steel, -40 to 93oC (-40 to 200oF), NEMA 1 (IP 10)
Storage Temperature Range -40 to 80oC (-40 to 176oF)
Operating Humidity Range 10 to 95% RH, non-condensing
Conductor Material Silver Plated Copper
Agency Approvals CE, RoHS2, WEEE

 

 

Transformers/Power Supplies
VA Rating Calculate based on load of devices.
Frequency 50/60 Hz
Over Current Protection Circuit Breaker
Dimensions 3.880 ̋ x 2.515 ̋ x 3.030 ̋ (w/ .500 ̋ NPT Hub)
Wire Length 9.5 ̋ Typical w/ .5 ̋ Strip
Operating Temperature -30 to 140° F
MTBF 100,000 Hours @ 77° F
Construction Split-Bobbin
Approvals

Class 2 UL5085-3 Listed, C-UL, CE, RoHS

 

Low Temperature/Refrigeration Temp Sensing Applications
Thermal Media Glycol  
Bottle Material/Cap Material Nalgene (HDPE) / Polypropylene  
Fluid Capacity 67 ml (2 oz)  
Bottle Dimensions: (Height x Diameter) 3.386” (86.00 mm) x 1.535” (39.00 mm)  
Cable Gland Material / Gland Material Polyamide 6 / Neoprene  
Cable Gland Torque Rating 1.66 Nm (14.7 lb. inch)  
Probe Size Accepted 0.098” to 0.256” (2.49mm to 6.50mm)  
Operating Temperature Range -40 to 120oC (-40 to 248oF)  
Thermal Media Glass Beads  
Bottle Material/Cap Material Nalgene (HDPE) / Polypropylene  
Fluid Capacity 67 ml (2 oz)  
Bottle Dimensions: (Height x Diameter) 3.386” (86.00 mm) x 1.535” (39.00 mm)  
Compression Fitting Material 316 Stainless Steel  
Probe Size Accepted 0.1875” (4.762 mm)  
Operating Temperature Range -100 to 120°C (-148 to 248°F)  
Thermal Media Glycol or Glass Beads  
Bottle Material/Cap Material Nalgene (HDPE) / Polypropylene w/ PTFE Foam Liner  
Fluid Capacity 250 ml (8.5 oz)  
Bottle Dimensions: (Height x Diameter) 4.04” (102.62 mm) x 2.18” (55.37 mm)  
Thermowell Material (3PT only) 316 SS Steel  
Probe Size Accepted 0.1875” (4.762 mm)  
Operating Temp Range – Glycol -40 to 120°C (-40 to 248°F)  
Operating Temp Range – Glass Bead -100 to 120°C (-148 to 248°F)  
Bracket Material 304 Stainless Steel  
Bracket Size( H x W x D) 2 oz Bottle: 2.541” (64.54 mm) x 1.500” (38.10 mm) x 1.760” (44.71 mm) 8.5 oz Bottle: 3.366” (85.49 mm) x 2.630” (66.80 mm) x 3.00” (76.20 mm)  
Mounting Screws / Material #10-16 Thread x 1/2” (12.7mm) / 410 Stainless steel  
Glycol Properties / Glycol Freezing Point Food Grade USP (Propylene Glycol); Non-Toxic -59°C (-74.2°F)
Glass Bead Properties / Glass Freezing Point Soda Lime Glass / NA  
Chemical Resistance Resistant to most acids, bases, and alcohols  
Bottle Sterility Lab Quality, Non-Sterile  
Storage Temperature Range -40 to 85°C (-40 to 185°F)  
Operating Humidity Range 10 to 100% RH, condensing  
Agency Approvals RoHS2, WEEE  

Note: In ALL low temperature sensing applications, a glycol buffer must be used.

 

Filter Pressure Switch
Contact (Load) Rating 300 VA pilot duty @ 115 to 277 VAC, 60 Hz; 15A non-inductive to 277 VAC, 60 Hz
Contact Arrangement SPDT w/ Automatic Reset
Maximum Pressure 0.5 PSI (0.03 Bar)
Life Expectancy AFS-222/AFS-262: 100,000 cycles minimum @ 1/2 psi (0.03 Bar) max pressure / cycle & max load
Operating Temperature Range -40 to 180oF (-40 to 82oC)
Operating Humidity Range 10 to 95% RH, non-condensing
Mounting Direction Any vertical plane
Enclosure Material Galvanized Steel
Electrical Connections Screw type terminal with cup washers
Dimensions (H x W x D) 6.25” x 4.46” x 3.18” (158.8 mm x 113.3 mm x 80.8 mm)
Agency Approvals UL, CUL, FM, CSA, CE, ISO 9001: 2008

 

Relays
Expected Relay Life Continuous Duty Coil 10 million cycles minimum mechanical
Operating Temperature -30 to 140° F
Humidity Range 5 to 95% (noncondensing)
Operate Time 20ms
Relay Status LED On = Activated (Recommended)
Approvals UL Listed, C-UL, CE, RoHS, UL916, UL Accepted for Use in Plenum, NEMA 1
Contact Ratings Rate based on required code and application
Coil Current

33 mA @ 10 Vac

35 mA @ 12 Vac

46 mA @ 24 Vac

55 mA @ 30 Vac

13 mA @ 10 Vdc

15 mA @ 12 Vdc

18 mA @ 24 Vdc

20 mA @ 30 Vdc

Coil Voltage Input 10-30 Vac/dc
Drop Out 2.1 Vac / 2.8 Vdc
Pull In 9 Vac / 10 Vdc