browse

| Overview

The HyperStat is part of Carrier's vertically integrated suite of intelligent building solutions, delivering multi-mode sensing, remote monitoring , and individual zone control for the comfort and productivity of building occupants, for more information refer to HyperStat Installation HyperStat UI

The HyperStat hardware is capable to work as a dependent device configured with a Carrier's CCU configured for various system-level profiles, or with any external Modbus or BACnet devices as a Modbus or BACnet slave, and it can also work as an independent or standalone device which can work as per profiles that can be configured in the HyperStat itself.

This software side support on the HyperStat device provides enhanced control of standalone equipment that is controlled and monitored by the Carrier solution for both modulating and multi-staged equipment.

The feature is introduced to address the HVAC needs of the customer who would like to use the Carrier's HyperStat alone for automating the HVAC operation based on certain profiles.

The profile supported for the standalone operation are.

  • CPU (Conventional Package Unit) 
  • HPU (Heat Pump Unit)
  • 2Pipe FCU (Fan Coil Unit)
  • 4Pipe FCU (Fan Coil Unit)

| HPU (Heat Pump Unit) Configuration

From the HyperStat home UI screen.

1.png

  • Press the + and - buttons together to navigate to the other screen of the hyperstat.

The inputs UI screen is displayed.

2.png

From the inputs UI screen.

  • Press the next button several times to reach the HVAC profile screen.

3.png

  • Press the down arrow 6.png button to navigate to the select profile option on the screen.

4.png

  • Press the select button to access the select profile.

5.png

  • Press the down arrow mceclip2.png button to select the HPU profile from the list available.

mceclip0.png

  • Press the back button to confirm the selection of the HPU profile and return to the HVAC profile screen.

7.png

  • Press the down arrow button twice to navigate to the Configure profile option.

8.png

  • Press the select button to access the Configure profile option, which opens the configuration options available for the HPU profile.

mceclip1.png

  • Press the down arrow to navigate to the configuration parameters under the HPU profile.

mceclip3.png

  • Press the select button to access the parameters options available under the different configurable relays, analogs, and other available options.

mceclip4.png

  • Press the down and up arrows to locate the required parameter to set for the relays, analogs, and other available options.

mceclip5.png

  • Press the deselect button to confirm the selection.

mceclip6.png

  • Repeat the above step to navigate, access, and select different parameter options for all the available relays, analogs, and others, till the desired configuration settings are met.
  • Refer to the Configuration Parameter table below for the parameter options available under different relays, analogs, and others and their purpose to help in the configuration.

mceclip7.png

mceclip8.png

mceclip9.png

|Configuration Parameters

Parameter

Purpose

Default Value

Values in the drop-down list

Relay 1 (Y1)

To enable compressors control stages/ Humification/ occupancy

Compressor Speed Stage 1

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Relay 2 (Y2)

 

 

To enable compressors control stages/ Humification/ occupancy

Compressor Speed Stage 2

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Relay 3 (G)

 

To enable compressors control stages/ Humification/ occupancy

Fan low speed

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Relay 4 (W1)

 

To enable compressors control stages/ Humification/ occupancy

Aux Heating Stage 1

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Relay 5 (W2)

To enable compressors control stages/ Humification/ occupancy

Fan High Speed

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Relay 6 (O/G)

 

To enable compressors control stages/ Humification/ occupancy

Type_O

Disable

Compressor stage 1

Compressor stage 2

Compressor stage 3

Aux Heating stage1

Aux Heating Stage2

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupancy Enable

Humidifier

Dehumidifier

Type_O

Type_B

Analog out 1

To enable compressor speed/ Fan speed/ / DCV damper

Compressor Speed

Disable

Compressor Speed

Fan Speed

DCV Damper

Analog out 2

To enable compressor speed/ Fan speed/ / DCV damper

Fan speed

Disable

Compressor Speed

Fan Speed

DCV Damper

Analog out 3

To enable compressor speed/ Fan speed/ / DCV damper

DVC Damper

Disable

Compressor Speed

Fan Speed

DCV Damper

Thermistor 1

To enable Airflow sensing

Airflow

Disable

Airflow

Thermistor 2

To enable door window open close sensing

Disable

Disable

Door/Window 1

Analog Input 1

To enable Keycard sensing/ Door window 2 sensing/

current consumed status sensing

Keycard

Disable

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Keycard

Door/Window 2

Analog Input 2

To enable Keycard sensing/ Door window 2 sensing/

current consumed status sensing

Current TX (0-20Amps)

Disable

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Keycard

Door/Window 2

Auto Away

To enable auto away capabilities

Disable

Disable

Enable

Analog Min 1

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog Max 1

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 

 

Analog Min 2

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog Max 2

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 

Analog Min 3

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog Max 3

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 
 
Previous
Next