| Overview
The Carrier ClimaVision MyStat Conventional Package Unit profile is a standalone profile that provides heating and cooling equipment controls for conditioning.
The Mystat provides the flexibility to choose between fully modulating and staged equipment control. Possible equipment configurations include:
-
2-stage cooling equipment control
-
2-stage heating equipment control
-
2-stage fan speed control
-
Linear and staged fans for cooling and heating equipment control
-
1 universal input
-
Fan Enabled and Occupied Enable
-
Humidifier and dehumidifier controls
| Wiring
| Configuration Steps
Before configuring the profile, you must first pair the MyStat to the CCU. See "Pairing to CCU" in MyStat Start-up.
Once paired, configure the profile parameters. See the table below. Then click Save.
| Parameter | Purpose | Default Value | Values in the drop-down list |
| Temperature Offset | To set the temperature offset value for the profile. | 0 (°F) | Range from -10 to + 10 in .1 increments |
| Auto Force Occupied |
To enable Auto force occupied Note: Auto Forced occupied/forced occupied and Auto-Away cannot work together. |
Disabled
|
Enable |
| Auto-Away |
To enable auto-away Note: Auto Forced occupied/forced occupied and Auto-Away cannot work together. |
Disabled
|
NA |
| Relay 1 | To enable staged conditioning controls | Cooling Stage 1 | Cooling Stage 1 Cooling Stage 2 Heating Stage 1 Heating Stage 2 Fan Low Speed Fan High Speed Fan Enable Occupied Enable Humidifier Dehumidifier Externally Mapped DCV Damper |
| Relay 2 |
To enable staged conditioning controls |
Fan Low Speed | |
| Relay 3 | To enable staged conditioning controls | Heating Stage 1 | |
| Relay 4 | To enable staged conditioning controls | Fan High Speed | |
| Analog Out | To enable modulating conditioning controls | Water Modulating Valve | Cooling Linear Fan Speed Heating Staged Fan Speed Externally Mapped DCV Modulating Damper |
| Universal In | To enable the supply water temperature measurement | Key Card Sensor (AI) | Supply Air Temperature Generic Alarm NO Generic Alarm NC Key Card Sensor (AI) Door/Window (N/C) - Title 24 Door/Window (AI) - Title 24 |
| Control System Object List
| Object Name | Type | Input/Output Type/Default Value |
| Heating Desired Temp | User Intent | NA |
| Cooling Desired Temp | User Intent | NA |
| Current Temp | Input | MyStat |
| Humidity | Input | MyStat |
| User Cooling Max Limit | User Intent | NA |
| User Cooling Min Limit | User Intent | NA |
| User Heating Max Limit | User Intent | NA |
| User Heating Min Limit | User Intent | NA |
| Conditioning Mode | User Intent | NA |
| Operation Mode | Input | NA |
| Fan Mode | User Intent | NA |
| Occupancy Mode | Input | MyStat Onboard |
| Cooling Stage 1 | Output | MyStat Relay |
| Cooling Stage 2 | Output | MyStat Relay |
| Fan Low Speed | Output | MyStat Relay |
| Fan High Speed | Output | MyStat Relay |
| Heating Stage 1 | Output | MyStat Relay |
| Heating Stage 2 | Output | MyStat Relay |
| Fan Enabled | Output | MyStat Relay |
| Humidifier | Output | MyStat Relay |
| Dehumidifier | Output | MyStat Relay |
| Modulating Cooling | Output | MyStat AnalogOut |
| Modulating Heating | Output | MyStat AnalogOut |
| Modulating Linear Fan Speed | Output | MyStat AnalogOut |
| Modulating Staged Fan Speed | Output | MyStat AnalogOut |
| Keycard Sensor | Input | MyStat Analog In |
| Door/Window Sensor | Input | MyStat Analog In |
| analogFanSpeedMultiplier |
Tuner |
1 |
| standalonehumidityHyteresis | Tuner | 5 %RH |
Note: For a comprehensive list of tuners and their details, refer to the Tuners Complete List.
| Sequence of Operation
The sequence of operation is driven based on Occupancy mode, Space Current Temperature, and the set Cooling and Heating Desired Temperatures.
The sections below describe the sequence of operations based on the occupancy modes, and how the other factors contribute to the sequence of operations during different types of occupancy modes.
| Occupancy Modes
The occupancy mode (Occupied or Unoccupied) is determined through a user-adjustable, graphical, seven-day schedule with a holiday schedule, alongside the configurable auto-away and forced occupied options (external schedule influencers) for optimized controls and enhanced energy savings.
Based on the above aspects factoring into the occupancy, the following can be the possible applicable occupancy modes:
-
Pre-conditioning
-
Occupied
-
Unoccupied
-
Auto-away
-
Forced Occupied
| Sequence of Operation During Pre-conditioning
Warm-up:
If the space temperature is below the occupied heating temperature setpoint, the pre-conditioning initiates the morning warm-up via HeatingLoopOutput.
The FanLoopOutput is enabled based on HeatingLoopOutput (FanLoopOutput= HeatingLoopOuptut* analogFanSpeedMultiplier(1)).
The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
Pre-cooling:
Suppose the space temperature is above the occupied space cooling temperature setpoint, the pre-conditioning shall initiate the morning pre-cooling via CoolingLoopOutput
The FanLoopOutput is enabled based on HeatingLoopOutput (FanLoopOutput= HeatingLoopOuptut* analogFanSpeedMultiplier(1))
The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
| Sequence of Operation During Occupied
At all occupied times: (based on a set schedule)
The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
-
A minimum fan speed is maintained
-
The minimum fan analog voltages are set to 2V (customizable) for linear fans
-
A recirculation fan speed voltage for staged fans
During Heating:
-
When the space current temperature falls below the Heating Desired Temperature the HeatingLoopOutput is enabled based on the difference in the space current temperature and heating desired temperature.
-
The FanLoopOutput is enabled based in HeatingLoopOutput (FanLoopOutput=HeatingLoopOutput* analogFanSpeedMultiplier(1))
During Cooling:
-
When the space current temperature is above Cooling Desired Temperature the CoolingLoopOutput is enabled based on the difference in the space current temperature and cooling desired temperature.
-
The FanLoopOutput is enabled based on CoolingLoopOutput (FanLoopOutput=CoolingLoopOutput* analogFanSpeedMultiplier(1))
-
When the space CO2 level is above the CO2 threshold set, the dcvLoopOutput is enabled with the dcvCalculatedDamperPos is determined by the loop calculated using the MyStat Co2 sensor & zoneCO2Threshold, modulating between the analogOutxAtMinDCVDamperPos and analogOutxAtMaxDCVDamperPos
Humidifier:
The humidifier modulates to maintain a return air humidity setpoint of 45% (adjustable), subject to the duct's high limit setpoint of 90% (adjustable). Humidification is locked out whenever the fan is de-energized or the duct humidity exceeds the high limit setpoint.
| Sequence of Operation During Autoaway
-
The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
-
The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
FanLoopOutput, HeatingLoopOutput, & CoolingLoopOutput, are disabled
During Heating:
- When the space current temperature falls below the heating autoaway setback temperature, the HeatingLoopOutput is enabled. based on the difference in the space's current temperature and the heating autoaway setback temperature.
- The FanLoopOutput is enabled based on HeatingLoopOutput (FanLoopOutput= HeatingLoopOuptut* analogFanSpeedMultiplier(1))
- The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
During Cooling:
- When the space current is above the cooling the CoolingLoopOutput is enabled. based on the difference in the space's current temperature and the cooling
- The FanLoopOutput is enabled based on CoolingLoopOutput (FanLoopOutput=CoolingLoopOuptut* analogFanSpeedMultiplier(1))
- The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
| Sequence of operation during unoccupied
- The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
- The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
FanLoopOutput, HeatingLoopOutput, & CoolingLoopOutput, are disabled
During Heating:
- When the space current temperature falls below the heating the HeatingLoopOutput is enabled based on the difference in the space's current temperature and the heating temperature.
- The FanLoopOutput is enabled based on HeatingLoopOutput (FanLoopOutput= HeatingLoopOuptut* analogFanSpeedMultiplier(1))
- The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
During Cooling:
- When the space current temperature is above the cooling the CoolingLoopOutput is enabled based on the difference in the space's current temperature and the cooling temperature.
- The FanLoopOutput is enabled based on CoolingLoopOutput (FanLoopOutput=CoolingLoopOuptut* analogFanSpeedMultiplier(1))
- The DCVLoopOutput based on the zone CO2 levels is disabled if configured.
| Sequence of Operation During Forced Occupied
The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
A minimum FanLoopOutput is enabled regardless of no conditioning.
During Heating:
- When the space current temperature falls below the Heating Desired Temperature the HeatingLoopOutput is enabled based on the difference in the space current temperature and heating desired temperature.
- The FanLoopOutput is enabled based on HeatingLoopOutput (FanLoopOutput= HeatingLoopOuptut* analogFanSpeedMultiplier(1))
- When the space CO2 level is above the CO2 threshold set, the dcvLoopOutput is enabled with the dcvCalculatedDamperPos is determined by the loop calculated using the sensor MyStatCo2 & zoneCO2Threshold, modulating between the analogOutxAtMinDCVDamperPos and analogOutxAtMaxDCVDamperPos
During Cooling:
- When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled, based on the difference in the space current temperature and cooling desired temperature.
- The FanLoopOutput is enabled based on CoolingLoopOutput (FanLoopOutput= CoolingLoopOuptut* analogFanSpeedMultiplier(1))
- When the space CO2 level is above the CO2 threshold set, the dcvLoopOutput is enabled. based on the following if enabled.
- If the Zone CO2 value > zoneCO2Threshold then the DCV damper control triggers based on the DCV loop output.
- If the Zone CO2 value < zoneCO2Threshold there will be no DCV damper trigger, and the relay will be set to OFF.
- When the space CO2 level is above the CO2 threshold set, the dcvLoopOutput is enabled with the dcvCalculatedDamperPos is determined by the loop calculated using the MyStatCo2 & zoneCO2Threshold, modulating between the analogOutxAtMinDCVDamperPos and analogOutxAtMaxDCVDamperPos
| Sequence of Operation During Emergency Dead
When building limits are violated, and the recorded temperature is within the building limit plus leeway the conditioning will happen in the direction of zone load.
| Sequence of Operation During Temp Dead
When the building temperature breaches the building limits beyond the leeway limits all the following loops are disabled:
- CoolingLoopOutput
- HeatingLoopOutput
- FanLoopOutput
- dcvLoopOutput
| Humidifier Control
The humidifier is turned ON whenever the humidity level for the system drops below the targetMinInsideHumidty set. The humidifier is turned OFF after being turned on when the humidity levels go humidityHysteresis above the targetMinInsideHumidty. Humidity control will not be maintained during UNOCCUPIED or VACATION modes.
| DeHumidifier Control
If the dehumidifier is selected, it turns ON whenever the humidity level for the system goes above the targetMaxInsideHumidty set. The dehumidifier will be turned OFF after being turned on when the humidity drops humidityHysteresis below the targetMaxInsideHumidty. Dehumidifier control will not be maintained during UNOCCUPIED or VACATION modes.
Note: The humidity level for the system is either the average level reported by all the zones serviced by the RTU/AHU.
| Control Mode Summary
| Modes & Operation | Pre-Conditioning | Occupied | AutoAway |
| Auto | (HeatingLoopOutput FanLoopOutput) /(CoolingLoopOutput FanLoopOutput |
(HeatingLoopOutput FanLoopOutput dcvLoopOutput) / (CoolingLoopOutput FanLoopOutput dcvLoopOutput |
(HeatingLoopOutput FanLoopOutput) / (CoolingLoopOutput FanLoopOutput) |
| Heat Only | HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput dcvLoopOutput |
HeatingLoopOutput FanLoopOutput |
| Cool Only | CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput dcvLoopOutput |
CoolingLoopOutput FanLoopOutput |
| Off | All Loops Deactivated | ||
| Modes & Operation | Unoccupied | Forced Occupied |
| Auto | (HeatingLoopOutput FanLoopOutput) / (CoolingLoopOutput FanLoopOutput |
(HeatingLoopOutput FanLoopOutput dcvLoopOutput) / (CoolingLoopOutput FanLoopOutput dcvLoopOutput) |
| Heat Only | HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput dcvLoopOutput |
| Cool Only | CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput dcvLoopOutput |
| Off | All Loops Deactivated | |
| Notes
-
When the Fan Enabled is configured alongside the AnalogOut-based Staged fan speeds, or Relay-based fan speeds.
-
The minimum Fan speed in an Analog-based fan configuration, or low fan speed in a Relay-based fan configuration is turned ON when the Fan loop output is <10% without considering the relay activation hysteresis.
-
When the door/window sensor is enabled, a minimum fan speed is operated when the door/window is open, and conditioning is OFF.
- In an Analog-based fan configuration, the fan is operated at the AnalogoutatMin, and in a staged fan speed configuration the fan is operated at the AnalogOutatRecirculate speed.
- A tuner parameter Minfanruntimepostconditioning defines the period for which the last known fan speed, in an analog-based fan configuration / minimum fan speed in a relay-based fan configuration, needs to run after the conditioning is turned off.